交流绝缘保护继电器

交流绝缘保护继电器

KRM16xE交流绝缘保护继电器(非接地交流系统)、KRM161x隔离交流绝缘跳闸继电器(旧款)

0.00
0.00
  

KRM16xE交流绝缘保护继电器(非接地交流系统)、KRM161x隔离交流绝缘跳闸继电器(旧款)

KRM16xE Series

KRM16xE - INSULATION RELAY FOR NON-GROUNDED AC SYSTEMS
  • Direct connection up to 690V line voltage, up to 6,6kV with HV adapter for both single or three phase systems

  • Monitoring during both live and standby conditions

  • For use in industrial, marine, offshore installations

  • "Easy view" status presentation

  • Immune to earth capacitance and voltage surges

  • Analogue output proportional to meter reading

  • Adjustable alarm setpoint


KRM161E
Scale range: 0-1000kΩ - ∞ (>6MΩ)
Direct connection up to 690V line voltage.
Up to 1,4kV via HV adaptor CH163x series.
Download Megacon KRM161x pdf
 
KRM163E
Scale range: 0-10MΩ -
 ∞ (>60MΩ)
Direct connection up to 690V line voltage.
Up to 6,6kV via HV adaptor CH163x or AN6,6 series.

Download Megacon KRM161x pdf

 

(OLD TYPE)

KRM161x - Isolated AC Insulation Trip RelayKRM161x
  • Insulation relay for non grounded systems

  • 0-660V Line Voltage. Up to 1400V with HV adapter

  • Non isolated analogue output (C-version)

  • "IDV" measuring principle


Description

KRM161B or KRM161C monitors resultant insulation level between a non-grounded single or three phase AC mains and its protective earth. It can monitor both live or non-live network.

The trip level is factory set and relay will operate after a delay of approximately two seconds. Relay is fail-safe and energises when powered. Link terminal 6 and 10 to make a non-latching relay.
 
Only ONE KRM16x can be connected to each IT-system.
 
KRM161B or KRM161C unit uses a superimposed DC monitoring voltage and so only one unit can be connected to each isolated system.